Loading...
Notecard Disconnected
Having trouble connecting?

Try changing your USB cable as some cables do not support transferring data. If that does not solve your problem, contact us at support@blues.com and we will get you set up with another tool to communicate with the Notecard.

Advanced Usage

The help command gives more info.

Connect a Notecard
Use USB to connect and start issuing requests from the browser.
Try Notecard Simulator
Experiment with the Notecard's API on a Simulator assigned to your free Notehub account.

Don't have an account? Sign up

Join Blues on June 3rd for Beyond the Prototype with Hello Everyday

Blues Developers
What’s New
Resources
Blog
Technical articles for developers
Connected Product Guidebook
In-depth guides for connected product development
Developer Certification
Get certified on wireless connectivity with Blues
Newsletter
The monthly Blues developer newsletter
Terminal
Connect to a Notecard in your browser
Webinars
Listing of Blues technical webinars
Blues.comNotehub.io
Shop
Docs
Button IconHelp
Support DocsNotehub StatusVisit our Forum
Button IconSign In
Docs Home
What’s New
Resources
Blog
Technical articles for developers
Connected Product Guidebook
In-depth guides for connected product development
Developer Certification
Get certified on wireless connectivity with Blues
Newsletter
The monthly Blues developer newsletter
Terminal
Connect to a Notecard in your browser
Webinars
Listing of Blues technical webinars
Blues.comNotehub.io
Shop
Docs
Example Apps
Samples
Building a Simple Asset Tracker
Building Edge AI Applications
Continuous Asset Tracking with External GPS and Immediate Location Sync
Managing a Notecard's WiFi Network Remotely
Putting a Host to Sleep Between Sensor Readings
Routing Data from Notehub to a Custom Cloud Endpoint
Sending Inbound Notes and Receiving Acknowledgment
Using LEDs and NeoPixels to Monitor Notecard Status
Accelerators
Asset Location Tracking
Heavy Equipment Hours-of-Use Utilization Tracker
Returnable Container and Tote Pool Tracker
Untethered Trailer and Chassis Fleet Tracker
Asset Performance Optimization
Legacy Diesel Generator Fleet Performance Uplift
Solar Array String-Level Performance Dashboard
Battery Management Systems
Aerial Lift Rental Equipment Battery Health Monitor
Off-Grid Solar Battery Site Controller
Remote Cabinet Backup Battery Sentinel
Downtime Prevention
Municipal Wastewater Lift Station Monitor
Rooftop HVAC Predictive Maintenance
VFD Pump Predictive Maintenance
Energy Monitoring Solutions
Commercial Tenant Sub-Metering Bridge
EV Charger Session Utilization Monitor
Utility Distribution Transformer Load Monitor
Energy Savings
Commercial Plug Load After-Hours Waste Dashboard
Demand Response Solar Battery Dispatcher
Multi-Site Walk-In Cooler Energy Setpoint Monitor
Industrial Equipment Monitoring
CNC Machine Spindle Load and Cycle Time Tracker
Injection Molding Shot-to-Shot Process Monitor
Trailer Manufacturer Connected Trailer Platform
Loss Prevention
Construction Equipment Anti-Theft Tracker with Immobilizer
Reefer Trailer Cold-Chain Door Event Monitor
Remote Patient Monitoring
Cellular Medication Adherence Pillbox
Post-Discharge Vitals Relay Hub
Remotely Monitored Assets
Off-Grid Livestock Water Tank Monitor
Remote Apiary Hive Health Monitor
Safety Assurance
Construction Site Environmental Noise Exposure Monitor
Lone Worker Panic and Fall Detection Beacon
Regulatory-Grade Pharmacy and Lab Cold Storage Audit Monitor
Supply Chain Tracking
Pallet-Attached Cold Chain Logger
Rail Car Condition Interchange Tracker
Truck Roll Reduction
Commercial Grease Interceptor Level Monitor
Propane LPG Tank Fill Telemetry
homechevron_rightExample Appschevron_rightAcceleratorschevron_rightRooftop HVAC Predictive Maintenance

Rooftop HVAC Predictive Maintenance

Rooftop HVAC Unit Predictive Maintenance Pack banner

note

This reference application is intended to provide inspiration and help you get started quickly. It uses specific hardware choices that may not match your own implementation. Focus on the sections most relevant to your use case. If you'd like to discuss your project and whether it's a good fit for Blues, feel free to reach out.

This project is a retrofit downtime prevention pack for commercial rooftop HVAC units. A handful of inexpensive sensors and a Blues Notecard Cell+WiFi turn an ordinary rooftop unit into a remotely-monitored, predictively-maintained asset — catching refrigerant loss, short-cycling, and clogged filters before the unit fails and a tenant loses cooling.

What you'll have when you're done: a weatherproof, line-powered sidecar bolted to a commercial rooftop air-conditioning unit that samples four sensors every minute, runs three failure-mode checks locally, and pages your on-call queue within ~60 seconds of a threshold trip — over cellular, with no site IT involvement and no modification to the unit itself. Hourly summaries are emitted on a separate event stream for trending and analytics. Operators can re-tune thresholds in the field from the cloud, with no firmware changes required.

1. Project Overview

The problem. In HVAC, an RTU (rooftop unit) is a self-contained packaged HVAC system — compressor, condenser, evaporator, blower, and controls all in one box — mounted on the roof of a commercial building. It's the workhorse of light commercial cooling: the vast majority of grocery stores, restaurants, strip-mall tenants, and small warehouses are conditioned by one or more RTUs sitting above the suspended ceiling.

A commercial RTU sits on a roof, cannot see building WiFi, and when it fails a grocery store or restaurant loses cooling and goes dark. The HVAC failures that cause most unplanned downtime aren't dramatic — they're gradual. A refrigerant leak slowly narrows the cooling delta-T over weeks. A tired contactor starts chattering, and the compressor short-cycles several times an hour instead of running in long, steady pulls. A neglected filter chokes airflow across the coil. None of these are invisible, but they're all easy to miss from inside the building — especially when nobody's looking. Each one is an impending failure detectable hours to days before the actual outage, if someone (or something) happens to be watching.

This project is that watcher. It's a retrofit sidecar that gets strapped to the RTU chassis on the roof, samples four sensors a minute, and pages the service technician before the walk-in cooler hits 50°F on a Saturday night. In Blues terms, it's a downtime-prevention device-to-cloud system: continuous remote monitoring on the edge, rule-based failure detection in firmware, and proactive-service alerts routed through Notehub to whatever on-call system the fleet owner already uses. The detection is heuristic — three scalar threshold checks, not a trained model, but it catches the impending-failure patterns HVAC technicians already look for on a service call.

Why Notecard. RTUs have no line-of-sight to indoor WiFi access points, and HVAC OEMs and service companies need a single SKU that works identically in a strip mall and in a warehouse. Cellular removes the per-site IT involvement entirely — there's no network form to fill out, no AP to pair to, and no IT ticket to chase. The Notecard Cell+WiFi variant keeps WiFi as an optional fallback for the occasional site that happens to have a rooftop-accessible AP, without compromising the cellular-first deployment model.

New to Blues?

Learn what we do in this 3-minute video that walks you through how we simplify wireless connectivity.

Learn what we do in this 3-minute video that walks you through how we simplify wireless connectivity.

Deployment scenario. A weatherproof enclosure strapped to the RTU frame, powered from 120VAC line at the RTU service disconnect (or from the 24VAC control transformer with an alternate supply. See Limitations), with four pigtails running into the unit: two thermistors (supply and return ducts), one clamp-on current transformer on the compressor hot leg, and one differential-pressure sensor with silicone tubes tapped across the filter. No RTU modification, no OEM cooperation, and no site IT coordination required.

2. System Architecture

System architecture: rooftop sensors → Notecarrier CX with Cygnet host → Notecard MBGLW → cellular/WiFi → Notehub → routes

Device-side responsibilities. Inside the sidecar, the Cygnet STM32 host on the Notecarrier CX wakes once a minute, sweeps the four sensors, and runs the three failure-mode checks before the rooftop unit has time to make a meaningful change. When it's done, it hands the resulting Note to the Notecard over I²C and uses card.attn to cut its own power until the next interval. No JSON marshaling, no AT commands, no serial buffers to babysit — the host is asleep more than 99% of the time it sits on the roof.

Notecard responsibilities. Everything the host queues up lands in the Notecard's on-device Notes store. Summary records ride out on the configured hub.set outbound cadence (default 60 minutes); any alert tagged sync:true skips the queue and the radio comes up immediately to ship it. The same Notecard also handles one-time GNSS site geolocation autonomously and pulls environment variables on every inbound sync, which is how a fleet operator retunes thresholds across a thousand rooftops without anyone touching firmware.

Notehub responsibilities. The Notecard's embedded global SIM gets it onto whichever carrier covers the rooftop, and from there events flow into Notehub, which ingests them, stores every one, and applies the project's routes. Alerts and summaries land in separate Notefiles on purpose — that lets you route rtu_alert.qo straight to an on-call paging service or CMMS (computerized maintenance management system) while rtu_summary.qo flows to a long-term analytics store without any filtering logic in the route itself.

Routing to the cloud (high level only). Notehub supports HTTP, MQTT, AWS, Azure, GCP, Snowflake, and several other destinations; route setup is project-specific. See the Notehub routing docs — this project doesn't ship any specific downstream endpoint.

3. Technical Summary

If you want the fastest path from "parts on the bench" to "first event in Notehub":

  1. Notehub — create a Notehub project, copy its ProductUID.
  2. Wire the bench rig — Notecarrier CX + Notecard MBGLW + two thermistor dividers on A0/A1 + CT bias network on A2 + SDP810 on I²C. Full pinout is in §5.
  3. Edit one line of firmware/rtu_predictive_maintenance/rtu_predictive_maintenance.ino — set PRODUCT_UID to your project's value (line 24).
  4. Flash — arduino-cli compile -b STMicroelectronics:stm32:Cygnet then arduino-cli upload. Full instructions in §7.1.
  5. Watch — open Notehub → your project → Events tab. You should see a _session.qo immediately, an rtu_summary.qo within an hour, and any threshold trips as rtu_alert.qo in real time.

The rest of this README expands each step and explains why the firmware is shaped the way it is. If you're doing a real rooftop install rather than a bench bring-up, also read §11 Limitations before you commit to a power topology.

Here is a sample Note this device emits:

{
  "supply_f": 52.4,
  "return_f": 71.8,
  "delta_t_f": 19.4,
  "compressor_amps": 14.7,
  "filter_dp_pa": 31.2,
  "starts": 3,
  "runtime_min": 41.0
}

4. Hardware Requirements

PartQtyRationale
Notecarrier CX1Integrated carrier with an embedded Cygnet STM32 host — no separate MCU needed for this sensor mix.
Notecard Cell+WiFi (MBGLW) / datasheet1Cellular removes per-site IT involvement; WiFi fallback is available for sites that happen to have it.
Blues Mojo (optional, bench-only)0–1Coulomb counter on the power rail for ground-truth energy validation during bench bring-up. Not required for production deployment. See §9 and §11.
10 kΩ NTC thermistor, β=3950, waterproof duct probe2Duct-mount supply and return air temperature for cooling delta-T.
10 kΩ 1% resistor (divider series leg)2Pull-up for each thermistor divider.
SCT-013-030 split-core CT, 30A / 1V AC (e.g. SparkFun SEN-11005) (current-output CT; add external burden resistor for 1 V_rms scaling)1Non-invasive compressor current sensing; 30A matches single-phase light-commercial RTU compressors.
TRRS 3.5 mm breakout (e.g. SparkFun BOB-11570)1The SCT-013's output lead terminates in a TRRS plug.
10 kΩ 1% resistor (bias pair)2CT bias circuit — centers the AC signal at Vref/2 so the ADC sees only positive voltages.
10 µF electrolytic capacitor1Bias-circuit decoupling.
Sensirion SDP810-125Pa differential-pressure sensor1I²C DP sensor across the filter; a continuous reading trends toward clogging, unlike a binary DP switch that only tells you once you're already there.
¼″ silicone tubing, ~2 ft1Taps the SDP810 across the filter frame.
AC/DC supply, 5V/2A output (e.g. MeanWell IRM-03-5)1Derives 5V DC from 120VAC line power at the RTU service disconnect for permanent grid-tied power. See Limitations for the 24VAC-input alternative.
NEMA 4X enclosure, ~6×4×2″1Rooftop-rated housing.

All Blues parts ship with an active SIM including 500 MB of data and 10 years of service — no activation fees, no monthly commitment.

5. Wiring and Assembly

Wiring diagram: thermistor dividers on A0/A1, CT bias circuit on A2, SDP810 on I²C, power chain from 120 VAC → 5 V supply → Mojo → +VBAT

All host I/O lands on the Notecarrier CX dual 16-pin header. The Notecard Cell+WiFi (MBGLW) seats into the carrier's M.2 slot; cellular, GNSS, and WiFi antennas are u.FL leads to roof-mounted externals. The Mojo sits inline between the 5V supply and the Notecarrier's +VBAT pad, and reports cumulative mAh to the Notecard over its Qwiic connector.

Pin-by-pin:

  • +3V3 → top of each thermistor's 10 kΩ series resistor, SDP810 VIO, top leg of the CT bias divider (10 kΩ from +3V3 to bias node).
  • GND → bottom of each thermistor NTC, SDP810 GND, bottom leg of the CT bias divider (10 kΩ from bias node to GND), bottom of the 10 µF bias-decoupling capacitor.
  • A0 → wiper (mid-point) of the supply-air thermistor divider.
  • A1 → wiper of the return-air thermistor divider.
  • A2 → CT signal node. The two 10 kΩ resistors form a divider from +3V3 to GND with the midpoint (the bias node) sitting at Vref/2 ≈ 1.65 V. The 10 µF capacitor connects from the bias node to GND — it decouples the bias rail to AC ground, not in series with the signal. The CT's TRRS plug bridges A2 and the bias node: tip → A2, sleeve → bias node (or vice versa; the AC signal is symmetric). A2 then sees 1.65 V DC with the CT's AC swing superimposed, keeping the signal inside the 0–3.3 V ADC window.
  • SDA / SCL → SDP810 SDA / SCL (the Notecarrier has pull-ups on-board).
  • +VBAT / +5V pad → Mojo LOAD output; BAT input of Mojo ← 5V DC from the AC/DC supply.

Mount probes inside the unit: supply thermistor ~12″ past the evaporator coil in the supply duct, return thermistor in the return plenum upstream of the filter, CT clamped on either of the hot legs feeding the compressor contactor (clamping only one leg is required, both will cancel), SDP810 tubes tapped across the filter frame with silicone tubing.

note

Note on the CT threshold default. compressor_on_amps = 3.0 is calibrated for typical light-commercial single-stage RTU compressors (3-to-5-ton, single phase, drawing ~12–25 A under load). On the smallest 1.5–2-ton units the in-rush-then-steady-state current can hover near 4–5 A, so 3 A is still a safe "compressor running" floor. For larger units the threshold is conservative and you may want to raise it via the compressor_on_amps env var to better separate "running" from "starting transient." See §6.

6. Notehub Setup

  1. Create a project. Sign up at notehub.io and create a project. Copy the ProductUID — it looks like com.your-company.your-name:rtu-pdm.

  2. Set the ProductUID in firmware. Open rtu_predictive_maintenance.ino and replace the empty string on the #define PRODUCT_UID "" line (around line 24) with your value. Alternative: pass it as a build flag (-DPRODUCT_UID=\"com.your-company.your-name:rtu-pdm\") if you'd rather not edit the source.

  3. Claim the Notecard. Power the assembled unit. On first cellular connect the Notecard associates itself with your Notehub project automatically — no manual claim step required. The device will appear in your project's Devices tab within a minute or two.

  4. Create a Fleet. Fleets (and Smart Fleets) are how Notehub groups devices for config and routing. One fleet per service territory is a reasonable starting point — it lets you set environment variables (thresholds) at the fleet level and override per-device if a given unit turns out to be unusual.

  5. Set environment variables. In Notehub, navigate to Fleet → Environment (or Device → Environment for a one-off override). Add any of the variables below; the device pulls them on its next wake (no reflash, no truck roll). All are optional — firmware defaults are shown.

    VariableDefaultPurpose
    delta_t_min_f12.0Supply/return delta-T °F below which delta_t_low fires (only evaluated while the compressor is actually running).
    short_cycle_starts_per_hour8Compressor starts per rolling hour above which short_cycling fires.
    filter_dp_alert_pa90.0Filter differential pressure (Pa) above which filter_dp_high fires.
    compressor_on_amps3.0Amps above which the compressor is considered running. Raise for larger 5+ ton units, lower only with care — the value also gates compressor-runtime accounting.
    sample_interval_sec60Seconds between samples.
    summary_interval_min60Minutes between summary Notes. Changing this also re-applies hub.set so the Notecard's outbound transmit cadence tracks the new value.
  6. Configure routes. At a minimum, add one route for rtu_alert.qo (to an on-call or CMMS endpoint) and a second for rtu_summary.qo (to a long-term store). Separating the two Notefiles at the source means you can fan them out to different destinations at different urgencies without any filtering in the route itself.

What you should see in Notehub

Within a minute of first power-on, the Events tab in your project should start populating. Three event kinds matter for this project:

  • _session.qo — automatic Notecard housekeeping events on each cellular session. Useful sanity check that the radio is reaching Notehub at all.
  • rtu_summary.qo — one per summary_interval_min. The body looks like:
    {
      "supply_f": 52.4,
      "return_f": 71.8,
      "delta_t_f": 19.4,
      "compressor_amps": 14.7,
      "filter_dp_pa": 31.2,
      "starts": 3,
      "runtime_min": 41.0
    }
    Any field reading -9999 means "no valid samples for this metric in the window" — treat as a sensor fault, not a near-zero measurement.
  • rtu_alert.qo — only emitted on a threshold trip, transmitted immediately. The alert field is one of delta_t_low, short_cycling, or filter_dp_high; the remaining fields carry the supporting numbers. See §8 for the per-alert payload shapes.

7. Firmware Design

Single sketch: firmware/rtu_predictive_maintenance/rtu_predictive_maintenance.ino.

7.1 Installing and flashing

Dependencies:

  • Arduino core for STM32 — stm32duino/Arduino_Core_STM32. Install via the Arduino Boards Manager (search "STM32 MCU based boards") or by adding the index URL https://github.com/stm32duino/BoardManagerFiles/raw/main/package_stmicroelectronics_index.json under File → Preferences → Additional Boards Manager URLs. The Notecarrier CX's onboard host is a Cygnet-class STM32L4 — select Generic STM32L4 series → Cygnet as the board.
  • Blues Wireless Notecard library — note-arduino. Install via the Arduino Library Manager, or arduino-cli lib install "Blues Wireless Notecard". Pin whatever current stable release the Library Manager offers at install time. See the note-arduino releases for the latest.

Flashing — Arduino IDE: open rtu_predictive_maintenance.ino, select the Cygnet board, hit Upload. The Notecarrier CX exposes the ST-Link interface on the same USB cable, so no external programmer is needed.

Flashing — arduino-cli: from the firmware directory,

# List installed STM32 boards to find the right FQBN for your installed core version
arduino-cli board listall | grep -i cygnet

# Then compile + upload (replace the FQBN below with what `listall` reported)
arduino-cli compile -b STMicroelectronics:stm32:GenL4:pnum=CYGNET rtu_predictive_maintenance.ino
arduino-cli upload  -b STMicroelectronics:stm32:GenL4:pnum=CYGNET -p /dev/cu.usbmodem* rtu_predictive_maintenance.ino

The exact FQBN is whatever the current stm32duino core ships for the Cygnet variant — the board listall command above is the authoritative source for your specific core version. Replace /dev/cu.usbmodem* with whatever port the Notecarrier enumerates as on your machine, typically COMx on Windows, /dev/ttyACM* on Linux.

After upload, open the serial monitor at 115200 baud to watch the [sample] lines fly by. The first wake will print [sample] once, hand off to the Notecard, and then the host powers off until the next interval, so don't be alarmed when the serial output goes quiet for ~60 seconds at a time.

7.2 Modules

ResponsibilityWhere
Notecard configuration (hub.set, templates, accelerometer quiet)hubConfigure, defineTemplates
Env-variable override fetch (per wake)fetchEnvOverrides
Thermistor / CT / SDP810 readingreadThermistorF, readCompressorAmps, readFilterDpPa
Threshold evaluation and alert emissionrunSampleCycle, sendAlert
Hourly summarysendSummary
Persistent state across sleep cyclesPersistState + NotePayloadSaveAndSleep / NotePayloadRetrieveAfterSleep

7.3 Sensor reading strategy

  • Thermistors. 16-sample average of 12-bit ADC counts, convert to resistance via the divider ratio, convert to temperature via the β equation, convert to Fahrenheit.
  • CT. The SCT-013-030 emits an AC signal. A 2-resistor divider with a 10 µF capacitor biases the signal to Vref/2 so the ADC sees only positive voltages. The firmware derives the DC offset from a 256-sample mean, then computes RMS over ~20 mains cycles (1480 samples) and scales at 30 A per volt RMS.
  • SDP810. I²C continuous measurement mode started once at boot; each read pulls three bytes (MSB, LSB, CRC) and divides by the 125 Pa variant's 240 count/Pa scale factor. The 500 Pa variant uses 60 count/Pa — don't mix the two up, the two variants share the same part family name.

7.4 Event payload design

One template-backed summary Note (rtu_summary.qo) shipped hourly; untemplated alerts (rtu_alert.qo) shipped immediately via sync:true. Templates matter here because an RTU pack running for 10 years on 500 MB has to respect its data budget — templated Notes travel as fixed-length records, not free-form JSON, and shrink the wire size by roughly 3–5×.

A quick refresher on the Note template format, which the snippet below uses: each numeric placeholder is a magic number whose integer part declares the wire type and whose fractional part declares the precision. 14.1 is a 4-byte IEEE-754 float kept to 1 decimal place; 12 is a 2-byte signed integer; 11 is a 1-byte signed integer; 18 is a 64-bit float. The Notecard rejects any subsequent note.add whose body doesn't match the registered shape, which catches firmware mistakes at the device rather than days later in your downstream pipeline.

Example alert body:

{
  "file": "rtu_alert.qo",
  "body": {
    "alert": "delta_t_low",
    "delta_t_f": 8.2,
    "supply_f": 48.1,
    "return_f": 56.3
  },
  "sync": true
}

7.5 Low-power strategy

Even with grid-tied power available, we still keep the host asleep most of the time — less heat in the enclosure, less wear on the supply, and a firmware pattern that ports directly to battery- or solar-powered variants without a rewrite. After each sample cycle the host calls NotePayloadSaveAndSleep, a note-arduino helper that serializes the in-RAM PersistState struct into Notecard flash and then issues a card.attn request configured to cut host power entirely for sample_interval_sec seconds. When ATTN re-fires, the Notecarrier re-applies host power, the MCU enters setup() from cold, and NotePayloadRetrieveAfterSleep pulls the saved struct back. From the firmware author's perspective, the sleep call looks like a single line — the Notecard does the rest.

The Notecard itself sits in its own low-power idle (~8 µA @ 5V) between cellular wakes. Sample rate and transmit rate are deliberately decoupled: we sample every 60 seconds but only transmit once an hour — alerts are the only thing that bypass the transmit timer.

7.6 Retry and error handling

  • The first Notecard transaction uses sendRequestWithRetry(req, 10) to paper over the cold-boot I²C race that the note-arduino library docs warn about.
  • Sensor reads returning NaN (unplugged probe, ADC rail pegged) are excluded from summary averages on a per-metric basis — each metric carries its own valid-sample counter so a single bad SDP810 read doesn't bias the thermistor averages. If a metric has zero valid samples in the window, the summary emits -9999 as a sentinel rather than a misleading zero.
  • The compressor-on branch also guards against evaluating delta-T when the unit is not actually cooling, so a perfectly-fine RTU idling overnight doesn't page anyone.
  • Env var changes to summary_interval_min re-apply hub.set on the next wake, so the Notecard's outbound cellular cadence stays in sync with local summary cadence rather than drifting apart.
  • Alert de-duplication via ALERT_COOLDOWN_SEC (30 minutes) prevents a slow-drifting sensor from paging the on-call every single sample — one alert per 30 minutes per failure mode is plenty.

7.7 Key code snippet 1: template definition

The template makes each summary Note a fixed-length record on the wire. 14.1 means 4-byte float; 12 means 2-byte signed integer.

J *req = notecard.newRequest("note.template");
JAddStringToObject(req, "file", "rtu_summary.qo");
JAddNumberToObject(req, "port", 50);
J *body = JAddObjectToObject(req, "body");
JAddNumberToObject(body, "supply_f",        14.1);
JAddNumberToObject(body, "return_f",        14.1);
JAddNumberToObject(body, "delta_t_f",       14.1);
JAddNumberToObject(body, "compressor_amps", 14.1);
JAddNumberToObject(body, "filter_dp_pa",    14.1);
JAddNumberToObject(body, "starts",          12);
JAddNumberToObject(body, "runtime_min",     14.1);
notecard.sendRequest(req);

7.8 Key code snippet 2: immediate-sync alert

sync:true tells the Notecard not to wait for the next outbound window — the Note jumps the queue and the radio wakes right away.

J *req = notecard.newRequest("note.add");
JAddStringToObject(req, "file", "rtu_alert.qo");
JAddBoolToObject(req, "sync", true);
J *body = JAddObjectToObject(req, "body");
JAddStringToObject(body, "alert", "delta_t_low");
JAddNumberToObject(body, "delta_t_f", delta_t);
JAddNumberToObject(body, "supply_f",  supply);
JAddNumberToObject(body, "return_f",  ret);
notecard.sendRequest(req);

7.9 Key code snippet 3: sleep between samples

NotePayloadSaveAndSleep persists state to the Notecard and then triggers card.attn which cuts host power. The next wake enters setup() fresh; NotePayloadRetrieveAfterSleep rehydrates the state.

NotePayloadDesc payload = {0, 0, 0};
NotePayloadAddSegment(&payload, STATE_SEG_ID, &state, sizeof(state));
NotePayloadSaveAndSleep(&payload, SAMPLE_INTERVAL_SEC, NULL);

8. Data Flow

Data flow: sensors sampled every 60s → three threshold rules → alert (sync:true) and summary (hourly templated) → Notehub → routes

Every 60 seconds the firmware runs one sample cycle, evaluates three independent threshold checks in parallel, and emits an alert for each one that trips. All three alerts converge onto the same rtu_alert.qo Notefile with sync:true, so any one failure mode paging out doesn't depend on the state of the other two.

  • Collected. Supply-air °F, return-air °F, compressor RMS amps, filter DP in Pa, compressor starts in the last rolling hour, cumulative compressor runtime.

  • Transmitted.

    • rtu_summary.qo — one record every summary_interval_min (default 60 minutes), template-encoded. Each numeric field is the average of its valid samples over the window; if a sensor produced zero valid reads that field carries the sentinel -9999 so downstream analytics can tell "sensor failed" apart from a real near-zero reading.
    • rtu_alert.qo — emitted only on a threshold trip, immediate sync, with a 30-minute dedup window per alert kind.
  • Routed. Both Notefiles go to Notehub and from there to whatever downstream the project's routes specify. The two filenames are deliberately separate so you can fan them out differently.

  • Alerts trigger on.

    • delta_t_low — cooling delta-T below delta_t_min_f while the compressor is drawing current (refrigerant loss indicator). Body: { alert, delta_t_f, supply_f, return_f }.
    • short_cycling — more than short_cycle_starts_per_hour compressor starts inside a true rolling 60-minute window (ring buffer of recent start timestamps). Body: { alert, starts_per_hour, compressor_amps }.
    • filter_dp_high — filter DP above filter_dp_alert_pa. Body: { alert, filter_dp_pa }.

    Each alert kind has its own 30-minute cooldown (ALERT_COOLDOWN_SEC), so a slow-drifting sensor can't page the on-call every minute. The three trips are independent: a unit can simultaneously be short-cycling and losing refrigerant, and you'll see one alert of each kind.

9. Validation and Testing

Expected cadence after deployment. In steady state, a correctly-behaving RTU generates one rtu_summary.qo event per hour and zero rtu_alert.qo events. Expect occasional alerts during the first week while you dial in thresholds for the specific unit — thermistor placement, duct geometry, and compressor model all nudge the baseline around.

Using Mojo to validate power behavior (optional bench step). The Notecard's published idle figure is roughly 8 µA @ 5V. See the low-power design guide for the authoritative measured numbers across Notecard SKUs and modes. Transmit bursts for a single small queued Note are on the order of tens of seconds at hundreds of mA peak on LTE Cat-1 bis, dominated by the radio warm-up and network registration. The host MCU, when cut by card.attn, draws essentially zero from the +VBAT rail.

A useful concrete target: with the defaults in this sketch (60-second sample, hourly transmit, host fully off between samples), expect on the order of 25–40 mAh / 24 h in steady state on cellular, dominated by the once-per-hour radio burst. Deviations of more than ~3× from that envelope are usually one of two things: the host isn't actually sleeping (continuous tens-of-mA baseline) or the radio is camping in registration (longer-than-expected hourly bursts on weak signal). Both are visible on a Mojo trace before they're visible anywhere else.

The Mojo reports cumulative mAh to the Notecard at 1% accuracy over its Qwiic link. A useful bench-up exercise: leave a unit running for 24 h powered from a known battery and confirm the Mojo tally lines up with the expected pattern — "host awake for a few seconds every minute, radio on for tens of seconds once an hour." That pattern is what you should see on a Mojo trace:

  • Healthy: flat baseline near zero, brief sub-second blips at the sample interval, one ~10–30-second burst at 100–300 mA per hour.
  • Host never sleeping: flat ~80–150 mA continuous baseline. Almost always a card.attn wiring or firmware regression (NotePayloadSaveAndSleep returning early, host code re-entering loop() repeatedly).
  • Weak signal / radio struggling: correctly-spaced hourly bursts but each burst is 60 seconds+ at peak. Move the cellular antenna or check site coverage.

Because the deployed RTU is grid-tied through the 120VAC service-disconnect supply, the absolute mAh number matters less in production than the shape of the trace. The bench measurement is still worth doing once per firmware revision — it's the cheapest way to catch a regression that silently keeps the host awake.

Mojo is not required for production deployment — it's a bring-up and CI-style regression tool. Once a firmware revision passes the trace check, the deployed units don't need it.

10. Troubleshooting

A short field guide for the things that actually go wrong on first bring-up.

SymptomLikely causeWhat to check
Device never appears in Notehub's Devices tab.PRODUCT_UID is empty or wrong, or the cellular antenna is disconnected / indoors.Re-verify PRODUCT_UID matches the Notehub project exactly. Move the unit outside or near a window. Check _session.qo events — none means no cellular connection.
Device appears, _session.qo events arrive, but no rtu_summary.qo ever shows up.All sensor reads are returning NaN, so sendSummary short-circuits via the any_valid guard.Open the serial monitor at 115200 baud and watch the [sample] lines. Any field reading nan indicates an unplugged or miswired sensor.
Thermistor reads pegged at one extreme.Probe is open (reads near +3V3) or shorted (reads near 0 V).The firmware returns NaN outside the valid divider range, so you'll see nan rather than misleading numbers. Check the divider wiring at A0 / A1.
compressor_amps always 0 even with the compressor running.CT is on the neutral leg or both hot legs (currents cancel), or the bias network is missing the 10 µF cap.Re-clamp the CT on one hot leg only. Verify the A2 bias node sits at ~Vref/2 (1.65 V) at idle.
filter_dp_pa reads NaN on every sample.SDP810 didn't ACK on I²C, or the address is wrong.Confirm the SDP810-125Pa is at 0x25 (some part variants use 0x26). Check pull-ups — the Notecarrier CX has them, but breakouts in line may add more.
Alerts firing constantly on a healthy unit.Thresholds aren't tuned for this unit yet.Raise delta_t_min_f toward 14–15 °F if the supply duct runs short, and watch one rtu_summary.qo per hour to see what the actual operating envelope looks like.
Mojo bench trace shows continuous tens of mA.Host isn't sleeping — card.attn isn't gating power.Confirm you're on a Notecarrier CX (which supports ATTN host gating); see §9 for trace shapes.

If a problem isn't on this list, the Blues community forum is generally the fastest place to get a second pair of eyes on a Notecard + sensor setup.

11. Limitations and Next Steps

This pack is deliberately a starting point — small, retrofittable, and aimed at the failure modes a single technician already knows how to recognize. A handful of things are out of scope on purpose, and a longer list of extensions makes sense once the basic detector is paying for itself.

Simplified for the POC:

  • Detection is rule-based — three scalar threshold checks, not a trained model. That catches the impending-failure patterns HVAC technicians already recognize on a service call, but it isn't the anomaly-detection or drift-analysis that a more sophisticated predictive-maintenance platform would layer on top.
  • CT readings are single-phase only. Three-phase commercial RTUs need three CTs and a firmware change to sum them.
  • The SDP810 CRC byte is read and discarded rather than verified — a communication-layer fault on the I²C bus won't be caught.
  • Compressor-start detection is sampled, not interrupt-driven: transitions that occur and finish entirely inside one sample_interval_sec window won't be counted. The 60-second default is well below normal RTU cycle times, but a badly-misbehaving contactor could in principle cycle faster than the sampler sees.
  • No local storage of historical samples — the Notecard does its own multi-day Note queue, but the sketch itself keeps only the current summary window in RAM plus a 16-slot ring buffer of recent compressor starts.
  • The 120VAC power path assumes the installer can tap the RTU service disconnect. Installations that can only offer the 24VAC control-transformer rail need a 24VAC-input supply instead (e.g. a Functional Devices PSH40A or a Mornsun LH05-23B05R3); the downstream 5V wiring is unchanged. A Scoop / solar variant is a reasonable addition for units where neither rail is practical.
  • Mojo is bench-validation equipment in this POC — the firmware does not read its LTC2959 coulomb counter over the Qwiic bus. Adding a runtime mAh field to the summary is a straightforward extension if fleet-level power telemetry is valuable.

Production next steps:

  • Three-phase CT support (or 208/240V split-phase) for larger units — a second and third CT on A3/A4 plus an RMS sum in firmware.
  • Add a duct-static-pressure sensor on the supply side to distinguish "clogged filter" from "blocked coil." The two look similar from the return side alone, but a clogged coil shows rising static on both sides while a clogged filter only rises on the return.
  • CRC check on all SDP810 I²C reads — the bytes are already there in the frame, the firmware just ignores them today.
  • Field-upgradeable firmware via Notecard Outboard DFU so a service company can push a threshold recipe or a new failure-mode detector to the entire fleet without a truck roll.
  • Per-unit commissioning: probe-offset correction via an environment variable. Thermistors drift a few degrees with duct placement, and calibrating once at install time is strictly better than living with the noise.
  • Weather-input overlay: correlate delta-T against outside-air temperature (via a Notehub environment variable sourced from a weather API route, or a dedicated outdoor-air probe) so refrigerant-loss detection isn't falsely triggered during mild-weather startup cycles, when delta-T naturally runs low before the coil saturates.

12. Summary

The service company that used to learn about a failed RTU from an angry grocer at 2 AM now gets a page hours earlier: refrigerant slowly leaking, a contactor starting to chatter, a filter approaching clog. Two thermistors, a clamp-on CT, an I²C pressure sensor, and a cellular Notecard turn an opaque rooftop box into an asset that tells on itself before tenants notice — and the same firmware drops onto the next rooftop, and the one after that, without an IT ticket or a site visit.

On This Page

  • 1. Project Overview
  • 2. System Architecture
  • 3. Technical Summary
  • 4. Hardware Requirements
  • 5. Wiring and Assembly
  • 6. Notehub Setup
    • What you should see in Notehub
  • 7. Firmware Design
    • 7.1 Installing and flashing
    • 7.2 Modules
    • 7.3 Sensor reading strategy
    • 7.4 Event payload design
    • 7.5 Low-power strategy
    • 7.6 Retry and error handling
    • 7.7 Key code snippet 1: template definition
    • 7.8 Key code snippet 2: immediate-sync alert
    • 7.9 Key code snippet 3: sleep between samples
  • 8. Data Flow
  • 9. Validation and Testing
  • 10. Troubleshooting
  • 11. Limitations and Next Steps
  • 12. Summary